Technical Data |
Over
Current |
Earth Fault |
Measurement |
True RMS |
Current Rating (ln) |
5A |
Current Setting Range (l>) |
20% - 250%
(1% step) |
2% - 50%
(1% step) |
Time
Setting Range (tl or TMl>) |
0.05 - 20.0
(0.1 sec step)
0.05 - 1.00
(0.01 time multiplier step) |
High
Set Range (l>>) |
20 - 2000%
(10% step) |
10 - 1000%
(10% step) |
High
Set Time Setting Range (tl>>) |
0.05 - 20.0
(0.1 sec step) |
IDMT
Graph |
Normal Inverse : 3.0 /
10
Normal Inverse : 1.3 / 10
Very Inverse
Extremely Inverse (0.64) |
Relay
Operation Level |
ln / ls >= 1.0 |
ln / ls >= 1.05 |
Display Range (ln) |
0.0% - 99.9% (0.1%
res.)
100% - 999% (1.0% res.)
1000% - 2000% (10.0% res.)
>2000% display 'out' |
Min
Sensitivity |
approx. 0.5% |
Tripping Contact |
SPDT 5A/240V AC |
Power
Supply |
240V AC, 50/60 Hz
(Optional: 110VAC 50/60Hz) |
C.T.
Input / Burden |
.../5A / <1VA |
Weight |
approx. 800g |
Ambient Temperature |
0°C to +70°C |
Standard |
IEC 1000-4-4, IEC
1000-4-5, IEC 255-5 |