Technical Data TM-8200s

TM - 8300s

Measurement True RMS
Current Rating (lE) 5A
Current Setting Range (lE>) 2% - 50%
Time Setting Range (tlE>) 0.05 - 10.0 sec
(0.1 sec step)
0.05 - 10.00 sec
(0.01 time multiplier)
High Set Range (lE>>) 10% - 500% 2 - 990% or OFF
High Set Time Setting Range (tlE>>) Fixed at 50 ms 0.05 - 10.0
(0.1 sec step)
IDMT Graph Normal Inverse : 3.0 / 10
Normal Inverse : 1.3 / 10
Very Inverse
Extremely Inverse (standard)
Extremely Inverse (0.64)
Long Time Inverse
Relay Operation Level ln / ls >= 1.0 ln / ls >= 1.0
Display Range (ln) 0.0% ~ 500% 0.0% ~ 990%
>990% display 'out'
Min Sensitivity approx. 0.5%
Tripping Contact
SPDT 5A/240V AC K1 : Latching
K2 : Programmable
Power Supply 240V AC, 50 Hz
(Optional: 110VAC 50 Hz)
240V AC, 50/60 Hz
(Optional: 110VAC 50/60 Hz)
C.T. Input / Burden .../5A / 1VA
Weight approx. 600g
Ambient Temperature 0°C to +70°C
Standard IEC 1000-4-4, IEC 1000-4-5, IEC 255-5

Copyright ©2003. Delab Scientific Sdn Bhd. ®All Rights Reserved.